mud <a href='https://www.ruidapetroleum.com/product/49'>pump</a> that gives sufficient flowrate but not enough pressure manufacturer

When choosing a size and type of mud pump for your drilling project, there are several factors to consider. These would include not only cost and size of pump that best fits your drilling rig, but also the diameter, depth and hole conditions you are drilling through. I know that this sounds like a lot to consider, but if you are set up the right way before the job starts, you will thank me later.

Recommended practice is to maintain a minimum of 100 to 150 feet per minute of uphole velocity for drill cuttings. Larger diameter wells for irrigation, agriculture or municipalities may violate this rule, because it may not be economically feasible to pump this much mud for the job. Uphole velocity is determined by the flow rate of the mud system, diameter of the borehole and the diameter of the drill pipe. There are many tools, including handbooks, rule of thumb, slide rule calculators and now apps on your handheld device, to calculate velocity. It is always good to remember the time it takes to get the cuttings off the bottom of the well. If you are drilling at 200 feet, then a 100-foot-per-minute velocity means that it would take two minutes to get the cuttings out of the hole. This is always a good reminder of what you are drilling through and how long ago it was that you drilled it. Ground conditions and rock formations are ever changing as you go deeper. Wouldn’t it be nice if they all remained the same?

Centrifugal-style mud pumps are very popular in our industry due to their size and weight, as well as flow rate capacity for an affordable price. There are many models and brands out there, and most of them are very good value. How does a centrifugal mud pump work? The rotation of the impeller accelerates the fluid into the volute or diffuser chamber. The added energy from the acceleration increases the velocity and pressure of the fluid. These pumps are known to be very inefficient. This means that it takes more energy to increase the flow and pressure of the fluid when compared to a piston-style pump. However, you have a significant advantage in flow rates from a centrifugal pump versus a piston pump. If you are drilling deeper wells with heavier cuttings, you will be forced at some point to use a piston-style mud pump. They have much higher efficiencies in transferring the input energy into flow and pressure, therefore resulting in much higher pressure capabilities.

Piston-style mud pumps utilize a piston or plunger that travels back and forth in a chamber known as a cylinder. These pumps are also called “positive displacement” pumps because they literally push the fluid forward. This fluid builds up pressure and forces a spring-loaded valve to open and allow the fluid to escape into the discharge piping of the pump and then down the borehole. Since the expansion process is much smaller (almost insignificant) compared to a centrifugal pump, there is much lower energy loss. Plunger-style pumps can develop upwards of 15,000 psi for well treatments and hydraulic fracturing. Centrifugal pumps, in comparison, usually operate below 300 psi. If you are comparing most drilling pumps, centrifugal pumps operate from 60 to 125 psi and piston pumps operate around 150 to 300 psi. There are many exceptions and special applications for drilling, but these numbers should cover 80 percent of all equipment operating out there.

The restriction of putting a piston-style mud pump onto drilling rigs has always been the physical size and weight to provide adequate flow and pressure to your drilling fluid. Because of this, the industry needed a new solution to this age-old issue.

Enter Cory Miller of Centerline Manufacturing, who I recently recommended for recognition by the National Ground Water Association (NGWA) for significant contributions to the industry.

As the senior design engineer for Ingersoll-Rand’s Deephole Drilling Business Unit, I had the distinct pleasure of working with him and incorporating his Centerline Mud Pump into our drilling rig platforms.

In the late ’90s — and perhaps even earlier —  Ingersoll-Rand had tried several times to develop a hydraulic-driven mud pump that would last an acceptable life- and duty-cycle for a well drilling contractor. With all of our resources and design wisdom, we were unable to solve this problem. Not only did Miller provide a solution, thus saving the size and weight of a typical gear-driven mud pump, he also provided a new offering — a mono-cylinder mud pump. This double-acting piston pump provided as much mud flow and pressure as a standard 5 X 6 duplex pump with incredible size and weight savings.

The true innovation was providing the well driller a solution for their mud pump requirements that was the right size and weight to integrate into both existing and new drilling rigs. Regardless of drill rig manufacturer and hydraulic system design, Centerline has provided a mud pump integration on hundreds of customer’s drilling rigs. Both mono-cylinder and duplex-cylinder pumps can fit nicely on the deck, across the frame or even be configured for under-deck mounting. This would not be possible with conventional mud pump designs.

Centerline stuck with their original design through all of the typical trials and tribulations that come with a new product integration. Over the course of the first several years, Miller found out that even the best of the highest quality hydraulic cylinders, valves and seals were not truly what they were represented to be. He then set off on an endeavor to bring everything in-house and began manufacturing all of his own components, including hydraulic valves. This gave him complete control over the quality of components that go into the finished product.

The second generation design for the Centerline Mud Pump is expected later this year, and I believe it will be a true game changer for this industry. It also will open up the application to many other industries that require a heavier-duty cycle for a piston pump application.

mud <a href='https://www.ruidapetroleum.com/product/49'>pump</a> that gives sufficient flowrate but not enough pressure manufacturer

Mud pump manufacturers frequently offer both types of pumps. In reality, the pump power end and fluid ends are identical. The difference lies with the method used by the pump to displace the mud.

In the early 1990s, it was generally accepted that the pumps used on mid-size and small boring machines should deliver fluid to the bore at a high pressure (1,800 to 2,200 psi/124 to 152 bar)) and have a low flow rate of 5 to 25 gpm (19 to 95 Lpm).

As the industry matured and operators became more experienced, it was found that a higher mud flow with lower pressures was the superior way to bore. In some formations high pressure, low flow is still preferred and provides the most success. However, in the majority of areas, higher flows are best to provide hole cleaning (removal of solids) and provide adequate bentonite for formation sealing and lubrication.

Plunger and packing technology is used when high (800 to 1,000 psi/55 to 69 bar and higher) pressures and lower flows are required. The flow pressure pushes on the front of the packing, compressing it tightly around the smooth surface of the reciprocating plunger sealing off leakage. When the pressure is below 800 to 1,000 psi (55 to 69 bar), there is insufficient flow pressure to assist in this sealing and packing leakage occurs. Leakage carries with it sand and other abrasive solids that lodge between the packing rings and plungers, causing rapid wear to the plunger surface and/or packing and making a good seal impossible.

One advantage of plungers/packing is that the packing can be adjusted by the operator to minimize leakage until the bore is complete and the pump can be serviced.

Pumps with piston/liner technology work in the opposite manner. Pistons work well to prevent leakage when flow pressures are low (below 1,200 psi/83 bar). Pistons are generally larger in diameter than plungers, allowing the pump to run slower-this is good-for the same flow rates.

Pistons have two disadvantages. First, when they fail or start leaking, the operator can do nothing to prolong operation until repairs can be made. Thus, repairs usually have to be made shortly after significant leakage starts. Second, pistons like to run cool and be lubricated. Thus, a piston cooling/lubrication system must be employed to add to piston life.

This system consists of a small centrifugal pump, spray nozzles, piping and collection tank. It sprays a mixture of water and lubricant (non-foaming soap or a small amount of liquid polymer), onto the back of the pistons.

Many boring machines are equipped with plunger pumps. These units are being applied where piston technology should be used, mainly low pressure and higher flows. These pumps frequently have leakage problems. To help operators combat leakage on these boring machines, conversion kits are being developed by some pump manufacturers to allow pumps to be changed from plunger to piston technology. Consult your boring machine or pump manufacturer for availability.

Economically, a good time to consider changing from plunger to piston technology on your pump is when the plungers are no longer serviceable and must be replaced. Conversion kits can be installed in the field and are considered bolt off bolt on upgrades.

If your mud pump has leakage problems, consider that you may be asking your pump to operate in a condition or application for which it was not originally designed.

mud <a href='https://www.ruidapetroleum.com/product/49'>pump</a> that gives sufficient flowrate but not enough pressure manufacturer

This website is using a security service to protect itself from online attacks. The action you just performed triggered the security solution. There are several actions that could trigger this block including submitting a certain word or phrase, a SQL command or malformed data.

mud <a href='https://www.ruidapetroleum.com/product/49'>pump</a> that gives sufficient flowrate but not enough pressure manufacturer

Your water pump is primed and the liquid is flowing… kind of. One of the more common problems with water pumps is a reduced or lower than expected water flow. When you need to dewater the jobsite, low flow means more downtime for the crew, costing money and putting deadlines at risk. Often, low water flow is less about your water pump and more to do with the situation. Below are a few things to review to troubleshoot water pump problems involving low water flow.

The greater the distance a pump has to pull the water, the lower the flow rate will be. Get too far from the water source and the more power is dedicated to ‘sucking’ the water and less to discharging, reducing the flow rate.

Typically, pumps should be with 20 feet of the water source. Depending on the typography, how high the pump is relative to the water, the flow may be reduced at even shorter distances. Your pump has individual specification, so be sure you read the spec and operate within them.

Your pump is designed to operate with a certain diameter input line. In some cases, we have seen people attach a smaller than recommended hose or line (using a reduction couplings). Depending on the intake line you use, it is also possible that the line crimps, or is “sucked in” on itself.

Debri blockage is a common problem. With murky water it can be hard to see the intake hose. But, operators should check to be sure there is no debris blocking the intake. The blockage usually happens at the filter as it does it’s job to prevent damage to the water pump. Remove the debri and reposition the hose to start pumping again.

The intake filter or screen can also be the culprit even without debri . While you must ensure the filter is fine enough to prevent damaging solids from entering the pump, too fine a filter for the water pump will restrict the flow right as the water enters the intake. Be sure the filter is proper for the pump.

Centrifugal water pumps are designed to operate with the impeller going in one direction. If it is going the opposite direction, the pump will not operate properly. This can happen if the electrical connections to the electric motor is not established correctly. Review the electric motors setup and user instructions to ensure your connections are correct.

Whether you are dewatering a jobsite, irrigating a field or applying your water pump for any other purpose, low flow is an issue. In some cases, like a firefighting pump, it can be a matter of life-or-death. One way to minimize onsite issue it to check all your equipment on a regular basis, replacing worn parts and performing maintenance as needed. But when confronted with low flow rates, follow the above steps and you’ll be able to get your water pump back in action, and your crew back to work.

mud <a href='https://www.ruidapetroleum.com/product/49'>pump</a> that gives sufficient flowrate but not enough pressure manufacturer

The 2,200-hp mud pump for offshore applications is a single-acting reciprocating triplex mud pump designed for high fluid flow rates, even at low operating speeds, and with a long stroke design. These features reduce the number of load reversals in critical components and increase the life of fluid end parts.

The pump’s critical components are strategically placed to make maintenance and inspection far easier and safer. The two-piece, quick-release piston rod lets you remove the piston without disturbing the liner, minimizing downtime when you’re replacing fluid parts.

mud <a href='https://www.ruidapetroleum.com/product/49'>pump</a> that gives sufficient flowrate but not enough pressure manufacturer

I am often asked to visit plant sites to consult on problems regarding inadequate flow rates in two-pump systems. These plants are usually more than 10 years old, and the commissioning operators and engineers are no longer present. Plant output requirements have increased, and/or the equipment is simply old and less efficient. Either way, the desired outcome is to obtain more flow through the system.

In a typical scenario, someone observes there is an additional installed pump and decides the solution is to simply start and operate the second pump. To an untrained person who sees two pumps installed in the same system, it seems logical that operating the second pump in parallel will increase the flow. This may work in some instances but often does not. When the system is not designed for two (or more) pumps to operate at the same time (in parallel), it will not take long for both pumps to experience issues.

Two pumps set up to run individually and/or in parallel. In other words, pumps can run in parallel or separately, covering a wide range of expected flows.

To find the solution to the problem, the first thing I ask for is the system curve. The curve is often not available, so I work with plant personnel to calculate and develop the system curve. Once we overlay the system curve on the pump curves, the issue and possible solutions become readily apparent.

In many cases, the system designer may have designed the system to have one pump do all of the required work (100 percent duty pump) with a second pump (also known as the redundant pump, installed spare, 100 percent spare or backup pump) ready for operation so the first pump can be removed from service without disturbing the production process. The pumps and their associated motors and controllers are each designed for 100 percent duty.

The intersection of the single pump curve and the system curve should be near the best efficiency point (BEP) for the pump. In these types of cases, the piping system is not designed for both pumps to operate at the same time. The pipe size is typically too small to efficiently handle the higher flows and presents a huge friction loss if both pumps are operated. Another way to think of this situation is the system curve is steep—not flat—for two-pump operation.

If the system is designed for both pumps to operate at the same time, then the system curve will, by design, be flatter overall and present less friction. You can also think of undesired friction as wasted horsepower, which translates to higher electrical costs.

This column is not meant to explain in detail why one curve is steep and the other is flat. The important point to note is the steeper curves represent more friction loss as you attempt to pump more flow through the pipe. For this article, it is sufficient to say that if the system is designed for parallel pumping, the system curve will tend to be flatter.

Figure 1 depicts a properly designed system for parallel pump operations. With one pump operating (Intersection Point 1), the system curve remains relatively flat, and flow is X with corresponding head Y.

When the second pump is started (Intersection Point 2), the friction presented by the higher flows yields a slightly steeper system curve. While the flow will be more than X, please note that it will not attain magnitude 2X.

Figure 2 shows that if one of the pumps is an installed spare and both pumps are operated at the same time, then the additional flow is too much for the given pipe diameter, and the result is a high friction loss.

Looking at Operating Point 2, you can see that starting the second pump has yielded little additional flow. It could be in the range of X flow plus 10 percent, but in many cases it is even worse. This is why starting the second pump can actually kill both pumps.

In these situations, there will always be a strong pump and a weak pump. Even if the pumps were designed and manufactured to be identical, there is always some nuance in one of the pumps and in the system that will prevent the pumps from being identical.

The stronger pump will attempt to take the full load (as presented by the system). The stronger pump will run far right on its curve (a condition called runout) and have issues with vibration and cavitation (net positive suction head [NPSH] and flow angle incidence recirculation) that will manifest as damaged impellers as well as short-lived bearings and mechanical seals. At the same time, the weak pump will run at low to no flow and have similar issues because it is operating at the far left side of the curve. It is not uncommon for the stronger pump to develop sufficient pressure to close the discharge check valve on the weaker pump, consequently forcing it to operate at a shutoff head (zero flow rate).

Figure 3 shows the operation of Pump 1 (Intersection Point 1) and the subsequent parallel operation of Pump 2. A common misunderstanding is that if you start the second pump, the flow rate will double to Intersection Point 2. In reality, the actual operating point will be at Intersection Point 3. In a centrifugal pump system, the pump will always operate where the system curve dictates.

Pumps in a system that is not designed for parallel operation should not be operated at the same time except for brief intervals during switching operations. To do otherwise is likely to prematurely damage both pumps.

Often, a good system design is to have pumps in parallel because they can provide flexibility to match the flow to the load. This setup is also more reliable because it provides standby protection for a relatively high percentage of the full load in the event of one pump loss.

Different pump designs/models can operate together in parallel, but it is important that they have an identical shutoff head and similar specific speeds.

If the system is designed for parallel pumps, determine which pump is the stronger one by running one at a time and measuring the head at various flows. As a general rule, always start the weaker pump first.

You can overcome some of the mismatches in pump and system designs by using variable speed drives and carefully monitoring where each pump is on the curve, changing speeds as required to keep the load balanced.

When running one pump for small loads and then starting the second pump to pick up larger loads, do not let the first pump run out on its curve too far before the second pump is started. The first pump may be cavitating for some time before the second pump picks up. I see this happen often on systems designed to operate automatically. The designer often overlooks the NPSH margins at the right side of the curve.

Whether the pumps are in parallel or it is just two pumps in a one-pump system, I always recommend installing hour meters to track the operating hours. I have witnessed many mistakes resulting from decisions based on someone"s memory or record-keeping habits. Hour meters are inexpensive insurance. (Do you know when to change the oil in the pump?)

In a parallel pump system, whichever pump is started first must be capable of covering the full load presented by the system curve without overloading the driver or running out on its own curve.

mud <a href='https://www.ruidapetroleum.com/product/49'>pump</a> that gives sufficient flowrate but not enough pressure manufacturer

Wells are generally drilled into the ground to recover natural deposits of hydrocarbons and other desirable materials trapped in geological formations in the Earth"s crust. A well is typically drilled using a drill bit attached to the lower end of a drill string. The well is drilled so that it penetrates the subsurface formations containing the trapped materials and the materials can be recovered.

At the bottom end of the drill string is a "bottom hole assembly" ("BHA"). The BHA includes the drill bit along with sensors, control mechanisms, and the required circuitry. A typical BHA includes sensors that measure various properties of the formation and of the fluid that is contained in the formation. A BHA may also include sensors that measure the BHA"s orientation and position.

Another aspect of drilling and well control relates to the drilling fluid, called "mud." The mud is a fluid that is pumped from the surface to the drill bit by way of the drill string. The mud serves to cool and lubricate the drill bit, and it carries the drill cuttings back to the surface. The density of the mud is carefully controlled to maintain the hydrostatic pressure in the borehole at desired levels.

One common method of communication is called "mud pulse telemetry." Mud pulse telemetry is a method of sending signals, either downlinks or unlinks, by creating pressure and/or flow rate pulses in the mud. These pulses may be detected by sensors at the receiving location. For example, in a downlink operation, a change in the pressure or the flow rate of the mud being pumped down the drill string may be detected by a sensor in the BHA. The pattern of the pulses, such as the frequency and the amplitude, may be detected by the sensors and interpreted so that the command may be understood by the BHA.

Mud pulse telemetry is well known in the drilling art. A common prior art technique for downlinking includes the temporary interruption of drilling operations so that the mud pumps at the surface can be cycled on and off to create the pulses. Drilling operations must be interrupted because the drill bit requires a continuous flow of mud to operate properly. Thus, drilling must be stopped while the mud pumps are being cycled.

Figure IA shows a prior art mud pulse telemetry system 100. The system 100 includes a mud pump 102 that pumps the mud from the surface, to the BHA 112, and back to the surface. A typical drilling rig will have multiple mud pumps that cooperate to pump the mud. Mud pumps are positive displacement pumps, which are able to pump at a constant flow rate at any pressure. These pumps are diagrammatically represented as one pump 102.

Mud from the mud storage tank 104 is pumped through the pump 102, into a standpipe 108, and down the drill string 110 to the drill bit 114 at the bottom of the BHA l 12. The mud leaves the drill string 1 10 through ports (not shown) in the drill bit 114, where it cools and lubricates the drill bit 114. The mud also carries the drill cuttings back to the surface as it flows up through the annulus 1 16. Once at the surface, the mud flows through a mud return line 118 that returns the mud to the mud storage tank 104. A downlink operation involves cycling the pump 102 on and off to create pulses in the mud. Sensors in the BHA detect the pulses and interpret them as an instruction.

Another prior art downlink technique is shown in Figure 1B. The downlink signal system 120 is a bypass from the standpipe 108 to the mud return line 118. The system 120 operates by allowing some of the mud to bypass the drilling system. Instead of passing through the drill string (110 in Figure IA), the BHA (112 in Figure IA), and returning through the annulus (116 in Figure I A), a relatively small fraction of the mud flowing through the standpipe 108 is allowed to flow directly into the mud return line 118. The mud flow rate to the BHA (not shown) is decreased by the amount that flows through the bypass system 120.

The full output of the mud pump 102 will flow to the BHA (not shown) during normal operations. When an operator desires to send an instruction to the BHA (not shown), a downlink signal may be generated by sequentially opening and closing the choke valve 124. The opening and closing of the choke valve 124 creates fluctuations in the mud flow rate to the BHA (not shown) by allowing a fraction of the mud to flow through the bypass 120. These pulses are detected and interpreted by the sensors in the BHA (not shown). The bypass system 120 may include flow restrictors 122, 126 to help regulate the flow rate through the system 120.

One advantage to this type of system is that a bypass system diverts only a fraction of the total flow rate of mud to the BHA. With mud still flowing to the BHA and the drill bit, drilling operations may continue, even while a downlink signal is being sent.

One aspect of the invention relates to a downlink system comprising at least one mud pump for pumping drilling fluid from a drilling fluid storage tank to a drilling system, a standpipe in fluid communication with the mud pump and in fluid communication with the drilling system, a return line in fluid communication with the drilling system for returning the drilling fluid to the drilling fluid storage tank, and a drilling fluid modulator in fluid communication with at least one of the group consisting of the standpipe and the return line.

Another aspect of the invention relates to a method of transmitting a downlink signal comprising pumping drilling fluid to a drilling system and selectively operating a modulator to create pulses in a drilling fluid flow. In some embodiments the modulator is disposed in a standpipe.

Yet another aspect of the invention relates to a drilling fluid pump controller comprising at least one actuation device coupled to a control console, and at least one connector coupled to the at least one actuation device and a pump control mechanism.

A still further aspect of the invention relates to a method for generating a downlink signal comprising coupling an actuation device to a pump control panel, coupling the actuation device to a pump control device on the pump control panel, and creating a pulse in a drilling fluid flow by selectively controlling the pump control device with the actuation device.

Another aspect of the invention relates to a downlink system comprising a drilling fluid pump in fluid communication with a drilling system, the drilling fluid pump having a plurality of pumping elements, and a pump inefficiency controller operatively coupled to at least one of the plurality of pumping elements for selectively reducing the efficiency of the at least one of the plurality of pumping elements.

Another aspect of the invention relates to a method of generating a downlink signal comprising pumping drilling fluid using at least one drilling fluid pump having a plurality of pumping elements, and creating a pulse in a drilling fluid flow by selectively reducing the efficiency of at least one of the plurality of pumping elements.

Another aspect of the invention relates to a downlink system comprising at least one primary drilling fluid pump in fluid communication with a drilling fluid tank at an intake of the at least one drilling fluid pump and in fluid communication with a standpipe at a discharge of the at least one drilling fluid pump, and a downlink pump in fluid communication with the standpipe at a discharge of the reciprocating downlink pump.

Another aspect of the invention relates to a method of generating a downlink signal comprising pumping drilling fluid to a drilling system at a nominal flow rate, and selectively alternately increasing and decreasing the mud flow rate of the drilling fluid using a downlink pump having an intake that is in fluid communication with a standpipe and having a discharge that is in fluid communication with the standpipe.

Another aspect of the invention relates to a downlink system comprising at least one primary drilling fluid pump in fluid communication with a drilling fluid tank at an intake of the at least one drilling fluid pump and in fluid communication with a standpipe at a discharge of the at least one drilling fluid pump, and an electronic circuitry operatively coupled to the at least one primary drilling fluid pump and adapted to modulate a speed of the at least one primary drilling fluid pump.

Another aspect of the invention relates to a method of generating a downlink signal comprising operating at least one primary drilling fluid pump to pump drilling fluid through a drilling system, and engaging an electronic circuitry that is operatively coupled to the at least one primary drilling fluid pump to modulate a speed of the at least one primary drilling fluid pump.

In certain embodiments, the present invention relates to downlink systems and methods for sending a downlink signal. A downlink signal may be generated by creating pulses in the pressure or flow rate of the mud being pumped to the drill bit.

The following terms have a specialized meaning in this disclosure. While many are consistent with the meanings that would be attributed to them by a person having ordinary skill in the art, the meanings are also specified here.

In this disclosure, "fluid communication" is intended to mean connected in such a way that a fluid in one of the components may travel to the other. For example, a bypass line may be in fluid communication with a standpipe by connecting the bypass line directly to the standpipe. "Fluid communication" may also include situations where there is another component disposed between the components that are in fluid communication. For example, a valve, a hose, or some other piece of equipment used in the production of oil and gas may be disposed between the standpipe and the bypass line. The standpipe and the bypass line may still be in fluid communication so long as fluid may pass from one, through the interposing component or components, to the other.

"Standpipe" is a term that is known in the art, and it typically refers to the high- pressure fluid passageway that extends about one-third of the way up a drilling rig. In this disclosure, however, "standpipe" is used more generally to mean the fluid passageway between the mud pump and the drill string, which may include pipes, tubes, hoses, and other fluid passageways.

A "drilling system" typically includes a drill string, a BHA with sensors, and a drill bit located at the bottom of the BHA. Mud that flows to the drilling system must return through the annulus between the drill string and the borehole wall. In the art, a "drilling system" may be known to include the rig, the rotary table, and other drilling equipment, but in this disclosure it is intended to refer to those components that come into contact with the drilling fluid.

In this disclosure, "selectively" is intended to indicate at a time that is selected by a person or by a control circuitry based on some criteria. For example, a drilling operator may select the time when a downlink signal is transmitted. In automated operations, a computer or control circuitry may select when to transmit a downlink signal based on inputs to the system.

Figure 2 shows a schematic of a downlink system in accordance with one embodiment of the invention. The system includes a bypass line 200 with a shutoff valve 204, a flow restrictor 205, a flow diverter 206, a modulator 210 coupled to a control circuitry 231, and a second flow restrictor 215. The bypass 200 is in fluid communication with the standpipe 208 at an upstream end and with the mud return line 218 on a downstream end. This arrangement enables the bypass line 200 to divert mud flow from the standpipe 208, thereby reducing the flow rate to the BHA (not shown).

The bypass system 200 includes a modulator 210 for varying the flow rate of mud through the bypass system 200. The frequency and amplitude of the flow rate changes define the downlink signal. One embodiment of a modulator will be described in more detail later, with respect to Figure 3A.

The downlink system in Figure 2 includes a shutoff valve 204. The shutoff valve 204 is used to isolate the bypass line 200 when no downlink signal is being transmitted. By closing the shutoff valve 204, the downlink system is protected from erosion that can occur when mud flows through the components of the system. When the bypass line 200 is in use, the shutoff valve 204 may be in a fully open position so that it will not be exposed to the high mud velocities that erode the choke valves (e.g., 124 in Figure I B) of the prior art. In a preferred embodiment, the shutoff valve 204 is disposed up stream of a flow restrictor (e.g., 205) so that the shutoff valve 204 will not experience the high mud flow rates present downstream of a flow restrictor.

Flow diverters and flow restrictors are components that are well known in the art. They are shown diagrammatically in several of the Figures, including Figure 2.

Those having skill in the art will be familiar with these components and how they operate. The following describes their specific operation in those embodiments of the invention that include either a flow restrictor or a flow diverter.

In some embodiments, a bypass line 200 according to the invention includes a flow restrictor 205. The flow restrictor 205 provides a resistance to flow that restricts the amount of mud that may flow through the bypass line 200. The flow restrictor 205 is also relatively low cost and easily replaced. This enables the flow restrictor 205 to be eroded by the mud flow without damaging more expensive parts of the system.

When the flow restrictor 205 is located upstream from the modulator 210, it may also serve as a pressure pulse reflector that reduces the amount of noise generated in the standpipe 208. For example, the modulator 210 may be used to create pulses in the mud flow. This has a side effect of creating back pulses of pressure that will propagate through the standpipe 208 and create noise. In drilling systems that also use uplink telemetry, noise may interfere with the detection of the uplink signal. A flow restrictor 205 will reflect a large portion of these back pressure pulses so that the standpipe 208 will be much less affected by noise.

It is noted that in the cases where the downlink sensors on the BHA are pressure transducers, it may be desirable to use a downlink system without a flow restrictor upstream of the modulator. Thus, some embodiments of a downlink system in accordance with the invention do not include a flow restrictor 205. Those having ordinary skill in the art will be able to devise a downlink system with selected components to fit the particular application.

In some embodiments, a downlink system in accordance with the invention includes a flow diverter 206 that is located upstream from the modulator 210. A flow diverter 206 may be used to reduce the amount of turbulence in the bypass line 202.

The flow diverter 206 is shown as a double branch flow diverter, but other types of flow diverters may be used. For example, a flow diverter with several bends may also be used. Those having ordinary skill in the art will be able to devise other flow diverters without departing from the scope of the invention.

A flow diverter 206 may be advantageous because the mud flow downstream of a flow restriction 205 is often a turbulent flow. A flow diverter 206 may be used to bring the mud flow back to a less turbulent flow regime. This will reduce the erosion effect that the mud flow will have on the modulator 210.

In some embodiments, the flow diverter 206 is coated with an erosion resistant coating. For example, a material such as carbide or a diamond coating could prevent the erosion of the inside of the flow diverter 206. In at least one embodiment, the flow diverter 206 includes carbide inserts that can be easily replaced. In this regard, the insert may be thought of as a sacrificial element designed to wear out and be replaced.

In some embodiments, a downlink system 200 in accordance with the invention includes a second flow restrictor 215 that is disposed downstream of the modulator 210.

The second flow restrictor serves to generate enough back pressure to avoid cavitation in the modulator 210. Cavitation is a danger because it affects the mud pulse signal and it causes severe erosion in the modulator 210. In situations where cavitation is not a danger, it may be advantageous to use embodiments of the invention that do not include a second or downstream flow restrictor 215.

Those having skill in the art will realize that the above described components may be arranged in a downlink system in any order that may be advantageous for the particular application. For example, the embodiment shown in Figure 2 may be modified by adding a second flow diverter downstream of the second flow restrictor 215. Those having ordinary skill in the art will be able to devise other component arrangements that do not depart from the scope of the invention.

Figure 3A shows an exploded view of a modulator 301 in accordance with the invention. The modulator 301 is positioned inside a pipe section 308, such as a bypass line or a standpipe. As shown in Figure 3A, the modulator 301 includes a rotor 302 and a stator 304 (or restrictor). Preferably, the rotor includes three passages 311, 312, 313 that allow fluid to pass through the rotor 302. The stator includes similar passages 321, 322, 323.

Typically, the rotor 302 and the stator 304 would be connected so that there is no gap or a small gap between them. A typical modulator may also include a motor (not shown in Figure 3A) to rotate the rotor 302.

As the rotor 302 rotates, the passages 311, 312, 313 in the rotor 302 alternately cover and uncover the passages 321, 322, 323 in the stator 304. When the passages 321, 322, 323 in the stator are covered, flow through the modulator 301 is restricted. The continuous rotation of the rotor 302 causes the flow restriction in the modulator 301 to alternately close to a minimum size and open to a maximum size. This creates sine wave pulses in the mud flow.

In some embodiments, such as the one shown in Figure 3A, the rotor 302 includes a central passage 331 that enables fluid to pass through the rotor 302. The stator 304 has a similar central passage 332. The central passages 331, 332 enable at least some flow to pass through the modulator so that the flow through the modulator 301 is never completely stopped.

In some embodiments, the passages 311, 312, 313 in the rotor 302 are sized so that they never completely block the passages 321, 322, 323 in the stator 304. Those having skill in the art will be able to devise other embodiments of a rotor and a stator that do not depart from the scope of the invention.

Figure 3B shows an exploded view of another embodiment of a modulator 351 in accordance with the invention. The modulator 351 includes two sections 361 and 371 that may be arranged to modulate the flow. For example, in one embodiment, section 371 comprises an inner segment that fits into the outer section 361. The modulator may then be installed in a pipe (not shown).

Flow through the pipe may be modulated by rotating one of the sections with respect to the other. For example, the inner section 371 may be rotated with respect to the outer section 361. As the windows 373 in the inner section align with the windows 363 in the outer section 361, the flow though the modulator 351 is maximized. When the windows 373 in the inner section 371 are not aligned with the windows 363 in the outer section 361, the flow through the modulator is minimized.

The modulator 351 may be arranged in different configurations. For example, the modulator 351 may be arranged parallel to the flow in a pipe. In such a configuration, the modulator 351 may be able to completely block flow through the pipe when the windows 363, 373 are not aligned. In some embodiments, the modulator is arranged so that fluid may pass the modulator in the annulus between the modulator 351 and the pipe (not shown). In those embodiments, the flow through the center of the modulator may be modulated by rotating one of the sections 361, 371 with respect to the other. In other embodiments, the modulator may be arranged to completely block the flow through the pipe when the windows 363, 373 are not aligned.

In some other embodiments, the modulator may be arranged perpendicular to the flow in a pipe (not shown). In such an embodiment, the modulator may act as a valve that modulates the flow rate through the pipe. Those having skill in the art will be able to devise other embodiments and arrangements for a modulator without departing from the scope of the invention.

One or more embodiments of a downlink system with a modulator may present some of the following advantages. A modulator may generate sine waves with a frequency and amplitude that are easily detectable by sensors in a BHA. The frequency of the sine waves may also enable a much faster transmission rate than was possible with prior art systems. Advantageously, a sine wave has less harmonics and generates less noise that other types of signals. Certain embodiments of the invention may enable the transmission of a downlink signal in only a few minutes, compared to the twenty to

Advantageously, certain embodiments of the invention enable a downlink signal to be transmitted simultaneous with drilling operations. This means that a downlink signal may be transmitted while drilling operations continue and without the need to interrupt the drilling process. Some embodiments enable the adjustment of the modulator so that an operator can balance the need for signal strength with the need for mud flow. Moreover, in situations where it becomes necessary to interrupt drilling operations, the improved rate of transmission will enable drilling to continue in a much shorter time.

Figure 4A shows another embodiment of a downlink system 400 in accordance with the invention. A modulator 410 is disposed in-line with the standpipe 408 and down stream of the mud pump 402. Instead of regulating the flow of mud through a bypass, the modulator 410 in the embodiment shown in Figure 4A regulates the pressure in the standpipe 408.

In the embodiment shown in Figure 4A, the downlink system 400 includes a flow diverter 406 downstream of the mud pump 402 and upstream of the modulator 410. The mud flow from the mud pump is often turbulent, and it may be desirable to create a normal flow regime upstream of the modulator 410. As was described above with reference to Figure 3A, the flow diverter 406 may be coated on its inside with an erosion resistant coating, such as carbide or diamonds. In some embodiments, the flow diverter 406 may include a carbide insert designed to be easily replaced.

The modulator 410 shown in Figure 4A is in parallel with a second flow restrictor 411. The second flow restrictor 411 enables some of the mud to flow past the modulator without being modulated. This has the effect of dampening the signal generated by the modulator 410. While this dampening will decrease the signal strength, it may nevertheless be desirable. The second flow restrictor 411 may enable enough mud to flow through the downlink system 400 so that drilling operations can continue when a downlink signal is being transmitted. Those having skill in the art will be able to balance the need for mud flow with the need for signal strength, when selecting the components of a downlink system.

In some embodiments, although not illustrated in Figure 4A, a downlink system includes a flow restrictor downstream of the modulator 410. In many circumstances, the drilling system provides enough resistance that a flow restrictor is not required.

in another embodiment, shown in Figure 4B, a downlink system 450 may be disposed in the mud return line 418. The embodiment shown in Figure 4B includes a flow diverter 406, a modulator 410 in parallel with a flow restrictor 411, and a down stream flow restrictor 415. Each operates substantially the same as the same components described with reference to Figure 4A. In this case, however, the downlink system 450 is located in the return line 418 instead of the standpipe (408 in Figure 4A).

The downlink system 450 is still able to modulate the mud pressure in the drilling system (not shown) so that the pulses may be detected by sensors in the BHA.

Advantageously, a downlink system disposed in the mud return linegenerates a very small amount of noise in the standpipe that would affect uplink transmissions.

One embodiment of a downlink control system 500 in accordance with the invention is shown in Figure 5A. An operator"s control console 502 typically includes pump control mechanisms. As shown in Figure 5A the pump control mechanisms may comprise knobs 504, 505, 506 that control the speed of the mud pumps (not shown).

Figure 5A shows three control knobs 504, 505, 506 that may control three mud pumps (not shown). A drilling system may contain more or less than three mud pumps.

Accordingly, the control console can have more or less mud pump control knobs. The number of control knobs on the control console is not intended to limit the invention.

A typical prior art method of sending a downlink system involves interrupting drilling operations and manually operating the control knobs 504, 505, 506 to cause the mud pumps to cycle on and off. Alternatively, the control knobs 504, 505, 506 may be operated to modulate the pumping rate so that a downlink signal may be sent while drilling continues. In both of these situations, a human driller operates the control knobs 504, 505, 506. It is noted that, in the art, the term "driller" often refers to a particular person on a drilling rig. As used herein, the term "driller" is used to refer to any person on the drilling rig.

In one embodiment of the invention, the control console 502 includes actuation devices 511, 513, 515 that are coupled the control knobs 504, 505, 506. The actuation devices 511, 513, 515 are coupled to the control knobs 504, 505, 506 by belts 512, 514, 516. For example, actuation device 511 is coupled to control knob 504 by a belt 512 that wraps around the stem of the control knob 504. The other actuation devices 511, 513 may be similarly coupled to control knobs 504, 505.

The actuation devices may operate in a number of different ways. For example, each actuation device may be individually set to operate a control knob to a desired frequency and amplitude. In some embodiments, the actuation devices 511, 513, 515 are coupled to a computer or other electronic control system that controls the operation of the actuation devices 511, 513, 515.

For example, the actuation devices 5 l l, 513, 515 may be magnetically coupled to the console 502. Other methods of coupling an actuation device to a console include screws and a latch mechanism. Those having skill in the art will be able to devise other methods for attaching an actuation device to a console that do not depart from the scope of the invention.

The actuation devices 511, 513, 515 may be coupled to the control knobs 504, 505, 506 by methods other than belts 511, 513, 515. For example, Figure 5B shows a pump control knob 504 that is coupled to an actuation device 521 using a drive wheel 523. The actuation device causes the drive wheel 523 to rotate, which, in turn, causes the stem 509 of the control knob 504 to rotate. In some embodiments, such as the one shown in Figure 5B, an actuation device 521 includes a tension arm 524 to hold the actuation device 521 and the drive wheel 523 in place. The tension arm 524 in Figure 5B includes two free rotating wheels 528, 529 that contact an opposite side of the stem 509 of the control knob 504 from the drive wheel 523.

Figure 5C shows another embodiment of an actuation device 531 coupled to a pump control lever 535. The actuation device 531 includes a drive wheel 533 that is coupled to the pump control lever 535 by a connecting rod 534. When the drive wheel 533 is rotated by the actuation mechanism 531, the lever 535 is moved in a corresponding direction by the connecting rod 534.

Figure 5D shows another embodiment of an actuation device 541 in accordance with the invention. The actuation device 541 mounts on top of the pump control lever 546. The actuation device 541 includes an internal shape that conforms to the shape of the pump control lever 546. As the internal drive 544 of the actuation device 541 rotates, the pump control lever 546 is also rotated.

One or more embodiments of an actuation device may present some of the following advantages. Actuation devices may be coupled to already existing drilling systems. Thus, an improved downlink system may be achieved without adding expensive equipment to the pumping system.

Advantageously, the mechanical control of an actuation device may be quicker and more precise than human control. As a result, a downlink signal may be transmitted more quickly and with a higher probability that the transmission will be correctly received on the first attempt. The precision of a mechanical actuation device may also enable sufficient mud flow and a downlink signal to be transmitted during drilling operation.

Advantageously, the mechanical control of an actuation device provides a downlink system where no additional components are needed that could erode due to mud flow. Because no other modifications are needed to the drilling system, operators and drillers may be more accepting of a downlink system. Further, such a system could be easily removed if it became necessary.

In some other embodiments, a downlink system comprises a device that causes the mud pumps to operate inefficiently or that causes at least a portion of the mud pumps to temporarily stop operating. For example, Figure 6 diagrammatically shows a pump inefficiency controller 601 attached to a mud pump 602a. Figure 6 shows three mud pumps 602a, 602b, 602c. Drilling rigs can include more or fewer than three mud pumps. Three are shown in Figure 6A for illustrative purposes.

Each of the mud pumps 602a, 602b, 602c draws mud from the mud storage tank 604 and pumps the mud into the standpipe 608. Ideally, the mud pumps 602a, 602b, 602c will pump at a constant flow rate. The pump inefficiency controller 601 is connected to the first mud pump 602a so that the controller 601 may affect the efficiency of the first mud pump 602a.

Figure 6B diagrammatically shows the internal pumping elements of the first mud pump 602a. The pumping elements of pump 602a include three pistons 621, 622, 623 that are used to pump the mud. For example, the third piston 623 has an intake stroke, where the piston 623 moves away from the intake valve 625, and mud is drawn from the mud tank into the piston chamber. The third piston 623 also has an exhaust stroke, where the piston 623 moves in the opposite direction and pushes the mud out an exhaust valve 626 and into the standpipe (608 in Figure 6A). Each of the other pistons 621, 622 has a similar operation that will not be separately described.

The first piston 621 includes a valve controller 628 that forms part of, or is operatively coupled to, the pump inefficiency controller (604 in Figure 6A). When it is desired to send a downlink signal, the valve controller 628 prevents the intake valve 627 on the first piston 621 from opening during the intake stroke. As a result, the first piston 621 will not draw in any mud that could be pumped out during the exhaust stroke. By preventing the intake valve 627 from opening, the efficiency of the first pump 603 is reduced by about 33%. The efficiency of the entire pumping system (including all three mud pumps 602a, 602b, 602c in the embodiment shown in Figure 6A, for example) is reduced by about 11 %.

By operating the pump inefficiency controller (604 in Figure 6A), the efficiency, and thus the flow rate, of the mud pumping system can be reduced. Intermittent or selective operation of the pump efficiency controller creates pulses in the mud flow rate that may be detected by sensors in the BHA.

One or more embodiments of a pump inefficiency controller may present some of the following advantages. An inefficiency controller may be coupled to any preexisting mud pump system. The downlink system may operate without the need to add any equipment to the pump system. The pump inefficiency controlled may be controlled by a computer or other automated process so that human error in the pulse generation is eliminated. Without human error, the downlink signal may be transmitted more quickly with a greater chance of the signal being received correctly on the first attempt.

Figure 7A diagrammatically shows another embodiment of a downlink system 700 in accordance with the invention. A downlink pump 711 is connected to the mud manifold 707 that leads to the standpipe 708, but it is not connected to the mud tanks 704. As with a typical mud pump system, several mud pumps 702a, 702b, 702c are connected to the mud tank 704. Mud from the tank is pumped into the mud manifold 707 and then into the standpipe 708.

Pumps also have a "discharge," where fluid is pumped out of the pump. In Figure 7A, the intake end of each of the mud pumps 702a, 702b, 702c is connected to the mud storage tank 704, and the discharge end of each of the mud pumps 702a, 702b, 702c is connected to the mud manifold 707. Both the intake and the discharge of the downlink pump 711 are connected to the mud manifold 707.

The downlink pump 711 shown in Figure 7A is a reciprocating piston pump that has intake and exhaust strokes like that described above with respect to Figure 6B. On the intake stroke, mud is drawn into the downlink pump 711, and on the exhaust stroke, mud is forced out of the downlink pump 711. The operation of the downlink pump 711 differs from that of the other pumps 702a, 702b, 702c in the mud pump system because it is not connected to the mud tank 704. Instead, both the intake and exhaust valves (not shown) of the downlink pump 711 are connected to the mud manifold 707. Thus, on the intake stroke, the downlink pump 711 draws in mud from the mud manifold 707, decreasing the overall flow rate from the mud pump system. On the exhaust stroke, the downlink pump 711 pumps mud into the mud manifold 707 and increases the overall flow rate from the mud pump system. In some embodiments, one valve serves as both the inlet and the discharge for the downlink pump. In at least one embodiment, a downlink pump is connected to the manifold, but it does not include any valves. The mud is allowed to flow in and out of the downlink pump through the connection to the manifold.

Selected operation of the downlink pump 711 will create a modulation of the mud flow rate to the BHA (not shown). The modulation will not only include a decrease in the flow rate-as with the bypass systems described above-but it will also include an increase in the flow rate that is created on the exhaust stroke of the downlink pump 711. The frequency of the downlink signal may be controlled by varying the speed of the downlink pump 711. The amplitude of the downlink signal may be controlled by changing the stroke length or piston and sleeve diameter of the downlink pump 711.

Those having ordinary skill in the art will also appreciate that the location of a downlink pump is not restricted to the mud manifold. A downlink pump could be located in other locations, such as, for example, at any position along the standpipe.

Figure 8 diagrammatically shows another embodiment of a downlink system 820 in accordance with the invention. The mud pumping system includes mud pumps 802a, 802b, 802c that are connected between a mud tank 804 and a standpipe 808. The operation of these components has been described above and, for the sake of brevity, it will not be repeated here.

The downlink system includes two diaphragm pumps 821, 825 whose intakes and discharges are connected to the mud manifold 807. The diaphragm pumps 821, 825 include a diaphragm 822, 826 that separates the pumps 821, 825 into two sections. The position of the diaphragm 822 may be pneumatically controlled with air pressure on the back side of the diaphragm 822. In some embodiments, the position of the diaphragm 822 may be controlled with a hydraulic actuator mechanically linked to diaphragm 822 or with an electromechanical actuator mechanically linked to diaphragm 822. When the air pressure is allowed to drop below the pressure in the mud manifold 807, mud will flow from the manifold 807 into the diaphragm pump 821. Conversely, when the pressure behind the diaphragm 822 is increased above the pressure in the mud manifold 807, the diaphragm pump 821 will pump mud into the mud manifold 807.

Figure 7 shows one piston downlink pump, and Figure 8 shows two diaphragm downlink pumps. The invention is not intended to be limited to either of these types of pumps, nor is the invention intended to be limited to one or two downlink pumps.

Figure 9 diagrammatically shows another embodiment of a downlink pump 911 in accordance with the invention. The discharge of the downlink pump 911 is connected to the mud manifold 907, and the intake of the downlink pump 911 is connected to the mud tank 904. The downlink pump 911 in this embodiment pumps mud from the mud tank 904 into the mud manifold 907, thereby increasing the nominal flow rate produced by the mud pumps 902a, 902b, 902c.

During normal operation, the downlink pump 911 is not in operation. The downlink pump 911 is only operated when a downlink signal is being sent to the BHA (not shown). The downlink pump 911 may be intermittently operated to create pulses of increased flow rate that can be detected by sensors in the BHA (not shown). These pulses are of an increased flow rate, so the mud flow to the BHA remains sufficient to continue drilling operations while a downlink signal is being sent.

One or more embodiments of a downlink pump may present some of the following advantages. A reciprocating pump enables the control of both the frequency and the amplitude of the signal by selecting the speed and stroke length of the downlink pump. Advantageously, a reciprocating pump enables the transmission of complicated mud pulse signals in a small amount of time.

A pump of this type is well known in the art, as are the necessary maintenance schedules and procedures. A downlink pump may be maintained and repaired at the same time as the mud pumps. The downlink pump does not require additional lost drilling time due to maintenance and repair.

Advantageously, a diaphragm pump may have no moving parts that could wear out or fail. A diaphragm pump may require less maintenance and repair than other types of pumps.

Advantageously, a downlink pump that is coupled to both the mud tanks and the standpipe may operate by increasing the nominal mud flow rate. Thus, there is no need to interrupt drilling operations to send a downlink signal.

In some embodiments, a downlink system includes electronic circuitry that is operatively coupled to the motor for at least one mud pump. The electronic circuitry controls and varies the speed of the mud pump to modulate the flow rate of mud through the drilling system.

One or more of the previously described embodiments of a downlink system have the advantage of being an automated process that eliminates human judgment an error from the downlink process. Accordingly, some of these embodiments include a computer or electronics system to precisely control the downlink signal transmission.

For example, a downlink system that includes a modulator may be operatively connected to a computer near the drilling rig. The computer controls the modulator during the downlink signal transmission. Referring again to Figure 2, the modulator is operatively coupled to a control circuitry 231. Those having skill in the art will realize that any of the above described embodiments may be operatively coupled to a control circuitry, such as a computer.

mud <a href='https://www.ruidapetroleum.com/product/49'>pump</a> that gives sufficient flowrate but not enough pressure manufacturer

However, even a properly installed pump can sometimes have problems, such aspriming, pressure, pulsation, noise or oil consumption problems.If you feel that the pump is not performing as it should, you must take immediate action to understand the cause of malfunctioning and restore it.

In this article we have summarized the most common problems that may occur during the normal use of a diaphragm pump and the necessary actions tofix them.

Don"t panic, before starting to dismantle your pump always check that the control regulator is in "by-pass" mode, this problem is very often due to inattention.

Problems on the suction line, i.e. pipes or fittings are sucking in air. The entire suction line must then be inspected and it must be ensured that pipes and fittings are securely fastened.

If the pressure continues to remain low or equal to zero, the problem may probably concern the nozzles; if the nozzles are worn or with a flow rate exceeding that which can be reached by the pump, they must be replaced.

The pulsation dampener may be set incorrectly. The dampener absorbs vibrations generated by the oscillating movement of the diaphragms thanks to a pressure chamber. If not set correctly, the dampener pressure can affect the pump pressure. Simply restore the correct pressure inside the dampener and the pump pressure will be regular again.

Another cause may be theincorrect configuration of the pressure regulator,check the pressure setting of the regulator (and if necessary, repair or replace it).

The diaphragms separate the pumping chamber from the transmission, preventing the pumped fluid from coming into contact with the mechanical parts and the oil; when the diaphragm breaks, the fluid filters in the oil making it milky.

Let"s now consider the damage that can occurto the diaphragms: in case of breakage of a diaphragm it is important to identify the cause and act to prevent its recurrence.

One of the most common causes is cavitation, vapor bubbles form inside the fluid which implode and ruin the diaphragm. To avoid cavitation there are several useful tips, first of all you should not suck water from excessive depths (maximum 4 meters).

mud <a href='https://www.ruidapetroleum.com/product/49'>pump</a> that gives sufficient flowrate but not eno
        </div>
    </div>

    <div class=